JCB2LE-40M 1P+N mini RCBO single Module residual current circuit breaker with overload protection 6kA
The JCB2LE-40M RCBOs (residual current circuit breaker with overload protection) are suitable for consumer units or distribution boards, applied under occasions such as industrial, and commercial, high-rise buildings and residential houses.
Exclusive design for your safety!
Electronic Type
Residual current protection
Overload and short circuit protection
Breaking capacity 6kA
Rated current up to 40A (available from 6A to 40A)
Available in B Curve or C tripping curves.
Tripping sensitivity: 30mA,100mA
Type A or Type AC are available
Double pole switching for complete isolation of faulty circuits
Neutral pole switching significantly reduces the installation and commissioning test time
Complies with IEC 61009-1, EN61009-1
Introduction:
JCB2LE-40M RCBO (residual current circuit breaker with overload protection) is designed for protection against short circuits, overloads and earth leakage in single phase installations. JCB2LE-40M RCBO is a combined RCCB and MCB in one unit providing earth leakage, overload and short circuit protection of domestic installations.
JCB2LE-40M RCBO combine MCB and RCD protection, provides overload and short circuit protection in one unit. It makes this a perfect unit for use in caravan parks, marinas, leisure parks by allowing earth fault protection to be restricted to a single circuit – limiting nuisance tripping of many circuits.
JCB2LE-40M rcbo provides combined residual current (earth leakage) protection and overload/short circuit protection in a single device and may be used to replace an RCCB/MCB combination. Movement characteristic of products can not be changed with outside mechanical tool;The operating organization has the free function to take off and buckle; Operate part can not be taken down from the shell outer of products, the shell can not influence the operating organization to work, the accessory group which replace the feelers pressure, should guarantee the feelers does not change while running.
JCB2LE-40M RCBO make you more safety.This RCBO with both disconnected neutral and phase guarantees its proper actuation against earth leakage faults even when the neutral and phase are wrongly connected. It automatically switches off the electrical circuit during the abnormal conditions of the network and faulty conditions to prevent damage. It has an energy limiting class 3, meaning the highest energy limiting performance to reduce risk of fire and other damage.
JCB2LE-40M RCBO is very easy to install in the single phase distribution box, it is non Line / Load sensitive RCBO, its Installation flexibility with the choice of line connection either from top or bottom.
JCB2LE-40M RCBO is the RCBO that has a width of 18 mm or 1-module housing and a short circuit capacity of 6kA. It is available in 6kA, type A, type AC, 30mA, 100mA with various current ratings from 6A to 40A.
The JCB2LE-40M RCBOs (residual current circuit breaker with overload protection) are suitable for consumer units or distribution boards, applied under occasions such as industrial, and commercial, high-rise buildings and residential houses. It is highly advised to be used in installations that requires high level of protection such as bathrooms, hospitals, kindergartens, etc.
Product Description:
The most important features
● Electronic Type
● Earth leakage protection
● Overload and short circuit protection
● Non Line / Load sensitive
● Breaking capacity up to 6kA
● Rated current up to 40A (available in 2A, 6A.10A,20A, 25A, 32A, 40A)
● Available in B Curve or C tripping curves.
● Tripping sensitivity: 30mA,100mA
● Type A or Type AC are available
● Compact SLIM module design, allows for more RCDs/MCBs to be installed in the one enclosure
● True Double Pole Disconnection in a Single Module RCBO
● Double pole switching for complete isolation of faulty circuits
● Neutral pole switching significantly reduces the installation and commissioning test time
● Insulated openings for easy busbar installations
● 35mm DIN rail mounting
● Installation flexibility with the choice of line connection either from top or bottom
● Compatible with multiple types of screw-drivers with combination head screws
● Meets ESV Additional Testing & verification requirements for RCBOs
● Complies with IEC 61009-1, EN61009-1
Technical Data
● Standard: IEC 61009-1, EN61009-1
● Type: Electronic
● Type (wave form of the earth leakage sensed): A or AC are available
● Poles: 1P+N
● Rated current:2A 6A, 10A, 16A, 20A, 25A, 32A, 40A
● Rated working voltage: 110V, 230V ~ (1P + N)
● Rated sensitivity I△n: 30mA, 100mA
● Rated breaking capacity: 6kA
● Insulation voltage: 500V
● Rated frequency: 50/60Hz
● Rated impulse withstand voltage(1.2/50) : 6kV
● Pollution degree:2
● Thermo- magnetic release characteristic: B curve, C curve, D curve
● Mechanical life: 20,000 times
● Electrical life: 2000 times
● Protection degree: IP20
● Ambient temperature (with daily average ≤35℃):-5℃~+40℃
● Contact position indicator: Green=OFF, Red=ON
● Terminal connection type:Cable/U-type busbar/Pin-type busbar
● Mounting: On DIN rail EN 60715 ( 35mm) by means of fast clip device
● Recommended torque: 2.5N.m
● Connection: From top or bottom are available
Standard |
IEC61009-1 , EN61009-1 |
|
Electrical features |
Rated current In (A) |
6, 10, 16, 20, 25, 32, 40 |
Type |
Electronic |
|
Type (wave form of the earth leakage sensed) |
A or AC are available |
|
Poles |
1P+N |
|
Rated voltage Ue(V) |
230/240 |
|
Rated sensitivity I△n |
30mA, 100mA,300mA |
|
Insulation voltage Ui (V) |
500 |
|
Rated frequency |
50/60Hz |
|
Rated breaking capacity |
6kA |
|
Rated impulse withstand voltage(1.2/50) Uimp (V) |
6000 |
|
Pollution degree |
2 |
|
Thermo-magnetic release characteristic |
B, C |
|
Mechanical features |
Electrical life |
2, 000 |
Mechanical life |
20, 000 |
|
Contact position indicator |
Yes |
|
Protection degree |
IP20 |
|
Reference temperature for setting of thermal element(℃) |
30 |
|
Ambient temperature (with daily average ≤35℃) |
-5...+40 |
|
Storage temperation (℃) |
-25...+70 |
|
Installation |
Terminal connection type |
Cable/Pin-type busbar |
Terminal size top/bottom for cable |
16mm2 / 18-5 AWG |
|
Terminal size top/bottom for Busbar |
10mm2 / 18-8 AWG |
|
Tightening torque |
2.5 N*m / 22 In-Ibs. |
|
Mounting |
On DIN rail EN 60715 (35mm) by means of fast clip device |
|
Connection |
From top or bottom are available |
Dimensions