JCB3-63DC Miniature Circuit Breaker 1000V DC
Miniature circuit breakers for use with DC voltages. Idea for communication systems and pv DC systems.
Exclusive design for your safety!
Short circuit and overload protection
Breaking capacity up to 6kA
With contact indicator
Rated current up to 63A
Rated voltage up to 1000V DC
1 Pole, 2 Pole, 3 Pole , 4 Pole are available
Comply with IEC 60898-1
Introduction:
JCB3-63DC miniature DC circuit breaker is designed for solar / photovoltaic PV system, energy storage and other direct current DC applications.They are mainly placed between batteries and hybrid inverters.
JCB3-63DC DC circuit breaker provides scientific arc extinguishing and flash barrier technology to fulfill quick and safe current interruption.
JCB3-63DC DC circuit breaker is a protective device equipped with both a thermal and an electromagnetic release that is available in 1 pole ,2pole, 3 pole and 4 pole versions. The switching capacity is 6kA according to IEC/EN 60947-2. The DC rated voltage is 250V per pole, rated voltage up to 1000V DC.
JCB3-63DC circuit breaker is available with rated currents of 2A to 63A.
JCB3-63DC dc circuit breaker offer new features, better connection, superior performance and increased levels of security. Its breaking capacity is up to 6kA.
JCB3-63DC dc circuit breaker can be locked (by a padlocking device) in OFF position as a safety measure for removal of the PV inverter
Since a fault current can flow in the reverse direction to the operating current, the JCB3-63DC Circuit breaker can detect and protect against any bidirectional current. To ensure the safety of the installation, it is necessary, depending on the various types of application, to combine the circuit breaker with:
• a residual current device at the AC end,
• a fault passage detector (insulation monitoring device) at the DC end
• an earth protection circuit breaker at the DC end
In all cases, fast action on site will be required to clear the fault (protection not ensured in the event of a double fault).WANLAI JCB3-63DC dc Circuit breakers are not polarity sensitive: (+) and (-) wires can be inversed without any risk. The circuit breaker is: delivered with three inter-pole barrier to provide increased isolation distance between two adjacent connectors
Product Description:
The most important features
● JCB3-63DC circuit breaker for DC applications
● Non-polarity, Easy wiring
● Rated voltage up to 1000V DC
● Rated switching capacity 6 kA according to IEC/EN 60947-2
● Insulation voltage Ui 1000V
● Rated impulse withstand voltage Uimp (V) 4000V
● Current limiting class 3
● Back-up fuse with high selectivity, thanks to low let-through energy
● Contact position indicator red – green
● Rated currents up to 63 A
● Available in1 Pole, 2 Pole, 3 Pole and 4 Pole
● 1 Pole=250Vdc, 2 Pole=500Vdc, 3 Pole=750Vdc, 4 Pole=1000Vdc
● Compatible with PIN or Fork type standard busbars
● Designed for Solar, PV, energy storage and other DC applications
Technical Data
● Standard: IEC60947-2, EN60947-2
● Rated current: 2A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A,
● Rated working voltage: 1P:DC250V, 2P:DC500V, 3P:DC 750V, 4P:DC1000V
● Rated breaking capacity: 6kA
● Pollution degree;2
● Rated impulse withstand voltage(1.2/50) : 4kV
● Thermo- magnetic release characteristic: B curve, C curve
● Mechanical life: 20,000 times
● Electrical life: 1500 times
● Protection degree: IP20
● Ambient temperature (with daily average ≤35℃):-5℃~+40℃
● Contact position indicator: Green=OFF, Red=ON
● Terminal connection type:Cable/Pin-type busbar
● Mounting: On DIN rail EN 60715 ( 35mm) by means of fast clip device
● Recommended torque: 2.5N.m
Standard | IEC/EN 60898-1 | IEC/EN 60947-2 | |
Electrical features |
Rated current In (A) | 1, 2, 3, 4, 6, 10, 16, | |
20, 25, 32, 40, 50, 63,80 | |||
Poles | 1P, 1P+N, 2P, 3P, 3P+N, 4P | 1P, 2P, 3P, 4P | |
Rated voltage Ue(V) | 230/400~240/415 | ||
Insulation voltage Ui (V) | 500 | ||
Rated frequency | 50/60Hz | ||
Rated breaking capacity | 10 kA | ||
Energy limiting class | 3 | ||
Rated impulse withstand voltage(1.2/50) Uimp (V) | 4000 | ||
Dielectric test voltage at ind. Freq. for 1 min (kV) | 2 | ||
Pollution degree | 2 | ||
Power loss per pole | Rated current (A) | ||
1, 2, 3, 4, 5, 6, 10,13, 16, 20, 25, 32,40, 50, 63, 80 | |||
Thermo-magnetic release characteristic | B, C, D | 8-12In, 9.6-14.4In | |
Mechanical features |
Electrical life | 4, 000 | |
Mechanical life | 20, 000 | ||
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Reference temperature for setting of thermal element(℃) | 30 | ||
Ambient temperature (with daily average ≤35℃) | -5...+40 | ||
Storage temperation (℃) | -35...+70 | ||
Installation | Terminal connection type | Cable/U-type busbar/Pin-type busbar | |
Terminal size top/bottom for cable | 25mm2 / 18-4 AWG | ||
Terminal size top/bottom for Busbar | 10mm2 / 18-8 AWG | ||
Tightening torque | 2.5 N*m / 22 In-Ibs. | ||
Mounting | On DIN rail EN 60715 (35mm) by means of fast clip device | ||
Connection | From top and bottom | ||
Combination |
Auxiliary contact | Yes | |
Shunt release | Yes | ||
Under voltage release | Yes | ||
Alarm contact | Yes |
Dimensions
Wiring diagram
Reliable cable protection
MCBs protect cables against damage due to overload and short circuits: In the event of dangerously high currents, the circuit breaker’s bimetallic thermal release will disconnect the power supply. In the event of a short circuit, the electromagnetic release will disconnect the power supply in a timely manner